Features:
1. Oil cup uses a three-electrode structure in line with GB / T5654-2007, the inter-electrode spacing of 2mm, can eliminate the impacts of stray capacitance and leakage impact on the dielectric loss test results. It has a drain solenoid switch, you can drain all the sample oil in the oil cup without removing the oil cup and rinse the oil cup with sample oil.
2. The instrument uses mid-frequency induction heating, PID temperature control algorithm. This heating method has some advantages, eg, oil cup and heating body non-contact, heating evenly and quickly, also easy to control, thus the temperature strictly controlled within the preset temperature range of error.
3. Internal standard capacitors for SF6 inflatable three-pole impact of capacitors, the capacitor dielectric loss and electrical capacity are not affected by ambient temperature, humidity, etc., to ensure that the instrument is still consistent accuracy after prolonged use.
4. AC Test Power Supply with AC-DC-AC conversion, effectively prevent affecting of the dielectric loss test accuracy for the mains voltage and frequency fluctuations, even the generator generate electricity, the instrument can also run properly.
5. Complete protection. When there is over-voltage, over-current, short-circuit for high-voltage, the instrument can be quickly cut off the voltage and warning. When the temperature sensor fails or is not connected, the instrument will give a warning message.
there is a limiting temperature relay amounted in the mid-frequency induction heating furnace, when the temperature exceeds 120 degrees, the relay release, then the heating stop.
6. Easy to set the parameters. Temperature setting range 0 ~ 125 °C, the AC voltage setting range 500 ~ 2200V, the DC voltage setting range 0 ~ 500V.
7. Large-screen LCD display with backlight, clear display. Friendly interface, simply follow the English menu prompt, enter the command, the instrument can be automatically tested. And automatically store and print test results.
8. With real-time clock, test date and time can be saved with the test results, display and print.
9. Empty electrode cup calibration. measuring capacitance and dielectric loss factor of empty electrode cup to determine the status of empty electrode cleaning and assembly of the cup. Calibration data is automatically saved, conducive to calculate the relative permittivity and DC resistivity precisely.